• PVC Insulated Copper Wire Building Wire System 1
  • PVC Insulated Copper Wire Building Wire System 2
PVC Insulated Copper Wire Building Wire

PVC Insulated Copper Wire Building Wire

Ref Price:
get latest price
Loading Port:
China Main Port
Payment Terms:
TT or LC
Min Order Qty:
-
Supply Capability:
-

Add to My Favorites

Follow us:


OKorder Service Pledge

Quality Product, Order Online Tracking, Timely Delivery

OKorder Financial Service

Credit Rating, Credit Services, Credit Purchasing

1. Product Description:

1. building electric cables wire Appliation

Cables used for communication system, its rated voltage should be at least equal to the system of nominal voltage, In dc system, nominal voltage should not greater than 1.5 times of rated voltage, System allows more than nominal voltage working voltage by 10%.

 

2. Product Characteristic:

(1)cables long-term allowed no more than 70°c, BV - 90 shall not exceed 90 Celsius temperature , the installation should not below 0°c Celsius temperature .

(2) cable permissible min. bending radius: less than 25 mm of exterior cable should be no less than 4 times of cable diameter, if for 25 millimeters, wire bending radius should not less than 6 times of cable diameter.

(3) wire and cable length of knitting or into the dish for 100 meters, length error of 0.5 meters

 (4) RV - 90 long-term allowed no more than 90 °c

 

3.Specification

Type

Name

Laying place and requirement

Crated voltage

Nominal Section (mm2

227IEC01(BV)

Copper conductor PVC insulated wires

Aluminum conductor PVC insulated wires

Fixed laid indoors

Conduit etc.

450/750

300/500

450/750

1.5...185

227IEC05 (BV)

0.5...1

BLV

2.5...185

227IEC07(BV-90)

Heat resistant copper conductor PVC insulated wire at 900C

Mainly be laid at the places of high temperature environment and can be laid indoors ,conduits.

300/500

0.5...2.5

BVR

Copper conductor PVC insulated flexible cable

Be for laying permanent place where flexible required.

450/750

2.5...150

BLVV

Aluminum conductor PVC insulated PVC sheathed round wires

 

Fixed laid, fit for the places with high mechanical protection and moisture place, can be laid in the air or underground.

BVVB

Copper conductor PVC insulated PVC sheathed flat wires

300/500

1...10

BLVVB

Aluminum conductor PVC insulated PVC sheathed flat wires

300/500

2.5...10

227IEC02(RV)

227IEC06(RV)

Copper conductor PVC insulated flexible connector wire

Mainly used at middle and light style moving electronics, home appliances, power and lighting and the places where flexible required

450/750

300/500

1.5...240

0.3...1

227IEC42(RVB)

Copper conductor PVC insulated flat flexible connector wire

300/300

0.3...1.5

 

4. Reference Picture

 

Q:i want to connect another wire to it how do i do it?
depends on the wire and what is on it. It may be as easy as soldering a wire to it, or buying a parallel connector adaptor of some sort. A 11kV power line, that requires special tools and lots of precautions. And permissions. .
Q:Upstairs toilet water seepage for a long time, my house is a large number of walls, has been unable to discuss the argument, the recent short circuit, and suspected to be the reason for water seepage, but upstairs and his insistence, even if there is a leaking can not affect wire. Because of this ignorant, so here to ask you, leakage of water will lead to short wire inside the wall? Thank you for answering. Question added: 1: is the old house, the wire is replaced seven years ago. 2: upstairs tenants insist on not admit leaking, but also invited his decoration master to see, they say no matter what the situation, even if the water leakage will certainly not lead to short circuit. For his argument doubt, so I would like to ask, is not any case, the leakage of water will not be inside the wall bubble to a short circuit? More
According to the hardware structure of the connected hardware can be divided into rack and cabinet 4 According to the installation method to divide, can be divided into wall and floor type 5 According to the connection hardware installation Location: Building patch panel (CD ), Building patch panels (BD) and floor patch panels (FD)
Q:i have a main service panel that was probably installed in the 70s or 80s. there is a bus bar on the right side that all of the white neutral wires terminate into. (there is also a bus bar on the left side, that is totally empty.) there are no bare copper ground wires visible anywhere in the box. the circuits all run from under the crawl space into exterior junction boxes on the siding, then up through metal conduit into the panel. i know some of the circuits are older, but some were added just in the last couple of years, and were done with permits. so how and where might the circuits be grounded?
There has to be a ground or it wouldn't have passed inspection. Look for a copper rod in the ground around the front of the panel, or to a cold water pipe. That is how many are grounded.
Q:A two-color air-conditioning, a 1.5P air-conditioning, two TV sets, a water heater, a Yuba, a hood, a washing machine, a refrigerator, there are some normal use of lights and other appliances, housing area is 85 square meters (The actual use of the area is 70 square meters), I would like to ask how many holes in the wall of the single-strand copper wire, about how many meters, thank you!
Because there is no plan to talk about the proportion of air conditioning alone to go to the total gate 2.5X2 + 1.53 Road bathroom outlet single walk 2.5X2 + 1.5 kitchen socket single walk 2.5X2 + 1.5 refrigerator single walk 2.5X2 + 1.5 all lights all the way 2.5X2 + 1.5 remaining socket 2.5X2 + 1.5 money on the 4 square X2 + 2.5 square
Q:I would like to wire two wall sconces on either side of my fireplace. I was planning on continuing the electrical circuit from a wall outlet located near the fireplace and including an inline switch. The outlet is on the left side of the fireplace so I was planning on running the wire 6 feet strait up from the outlet, over three feet, installing a new electrical box and mounting the sconce. The question I have is, how can I run the wire to the other sconce on the right side of the fireplace. Can I run the wire in the wall in front of the fireplace? Also is there any electrical codes that require switches to be a certain height off the floor? I live in southern California.
you want Your switch box to be the same height as your other switches in the room as for getting from one sconce to another if the fire place is ont he 1st floor and the basement ceiling isn't sheet rocked i would suggest drilling a hole from the basement making sure your in the wall send a snake from the basement to where you plan on putting the sconce on the left side pull the wire to the basement cut in your box for the sconce on the right side drill another hole from the basement making sure again your in the wall send the snake up to the hole you cut in on the right side that is the easiest way with the least amount of damage but make sure you measure correctly so if you drill up you don't come through the floor
Q:how many wires are allowed in a standard outlet box (i believe 3x2 1/2 deep). what do you do if you need more wires than are allowed?how many wires are allowed if i gang 2 boxes?i live in ontario, canada. thanks
In the US by the NEC, it depends on the size of the wires. 14 ga it is 2 cubic inches per conductor. 12 ga it is 2.25, and 10 is 2.5 cubic inches per conductor. Your box is 3 cubic inches if you measured it right so you can only put 1 14 wire in it. Since you seem unsure of what you are trying to do with box fill, call a qualified professional electrician to do the work.
Q:i was working on this car and somehow crossed these wires and it starting smoking really bad under the dashwell the lady had her dog in the car .to say the least the doors locked and flames were rolling by the kick panelwe couldnt get the dog out in time.is there a way to get my license back.i really like to work on cars
YOU my friend, are the unluckiest guy I have ever heard of! In 25 years of working on cars, I have NEVER heard of anyone losing their ASE certification. My guess is you won't get it back, because they must have found you seriously negligent to take such a severe step against you. If you feel you have been unjustly punished, contact an attorney. You may have grounds for legal action. the initial appointment is usually free, and sometimes you pay nothing unless your attorney wins. Good luck to you. That is an awful thing to happen to a professional mechanic.
Q:1) I want to install a ceiling light fixture (chandelier style) but I don't have a ceiling outlet box. 2) I want to convert the chandelier to a lamp that gets plugged into a regular outlet, so I have a) the chandelier w/ it's own cord (meant to be attached to the ceiling box) and b) 20 ft of regular cord attached on one end to a quick clamp plug.3) On the 20ft regular cord, and I can tell on this cord which wire is hot b/c one side is smooth (hot) and the other side is ribbed (neutral). Unfortunately, the cord from the chandelier itself is SMOOTH on all sides and is not marked white/black, smooth/ribbed, hot/neutral or with any other indicator that would allow me to tell which side is which. Hence, I don't know which chandelier wire to attach to which cord wire.Please help!
Check one of the sockets on the chandelier. The side of the socket is metal and so is the small contact on the bottom of the socket. The bottom piece is supposed to be the 'hot' side of the socket. It is a safety issue. It prevents you from touching the electrified part of the socket(the side part if it were wired backwards) when changing a bulb. That is the reason that the lamp cord has the ribbed and smooth sides -- to make sure that the bottom contact is hot and not the side --that applies to all lamp sockets.
Q:I am installing a new exhaust fan in my bathroom and along the joist I will be attaching it to, there is a black electrical wire that runs right along it. There is a bit of play in it, and I guess I can tack it upwards to move it out of the way, but was wondering what would be the best way to take care of this. I think the original installation had the fan either pinned up against the wire or had the wire sitting on top of the fan unit. The new fan unit is bigger, so I don't think it can sit on top of the box. Note: this wire is not the same wire that is providing electricity to the fan.
In the UK house wiring uses Red for live, Black for neutral and Earth is bare copper (sometimes with a green or green/yellow sleeve). Take care, I've seen wire colours used in correctly - always verify. If you are not 100% sure get a qualified electrician, bad/ inncorrect house wiring can be lethal. For a plug (flex) Brown live (usually fused), blue neutral, green/yellow Earth. If you cut an old plug top off take out the fuse - this way is someone plugs it in to a socket they won't be exposed to live mains.
Q:I can hear a small rodent within the walls of my bathroom. Now the power in my bathroom and bedroom is off. Could that rodent have eaten away at the wiring and caused the power to be off?
It's possible, yes. Although it could just be a blown fuse or something. Get an electrician to take a look.

1. Manufacturer Overview

Location
Year Established
Annual Output Value
Main Markets
Company Certifications

2. Manufacturer Certificates

a) Certification Name  
Range  
Reference  
Validity Period  

3. Manufacturer Capability

a)Trade Capacity  
Nearest Port
Export Percentage
No.of Employees in Trade Department
Language Spoken:
b)Factory Information  
Factory Size:
No. of Production Lines
Contract Manufacturing
Product Price Range

Send your message to us

This is not what you are looking for? Post Buying Request

Similar products

New products

Hot products


Hot Searches

Related keywords