XLPE Insulated and PVC Sheathed Low Voltage Power Cables
- Loading Port:
- China main port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 100 m
- Supply Capability:
- 20000 m/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
XLPE INSULATED PVC POWER CABLE 1KV TO 35KV
1 Information
a, Number of cores:
1, 2, 3, 3+1, 3+2, 3+3, 4, 4+1, 4+2, 5 and so on.
b, Construction:
Stranded copper conductor for single and shaped conductors for multi-core cables, XLPE insulated, PVC bedding, zinc plating steel wire armored and PVC sheathed cables.
c, Nominal Section
Area(mm2) :1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 800
2 Standard:
IEC60502,and BS6346, VDE, AS/NZS, UL,etc or as customer's request.
3 The Rated Voltage(kv):
1st class 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 21/35
2nd class 1/1 3/3 6/6 8.7/10 12/15 18/20 - 26/35
4 Application:
These cables are most suitable for direct burial or for installation on trays or ducts, Where there is
a risk of mechanical damage, armoured cables should be used.
5 Model and Name
China Type | Description | Application | |
Cu | Al | ||
YJV | YJLV | XLPE insulation PVC sheath power cable | To be laid indoors, in tunnel, cable furrow or pipe, the cable couldn't bear mechanical force outside |
YJY | YJLY | XLPE insulation PE sheath power cable | |
YJV22 | YJLV22 | XLPE insulation, steel tape armor, PVC sheath power cable | To be laid underground, the cable could bear certain mechanical force, but it couldn't bear great pulling force. |
YJV23 | YJLV23 | XLPE insulation, steel tape armor, PE sheath power cable | |
YJV62 | YJLV62 | XLPE insulation, no magnetism steel tape armor, PE sheath power cable | |
YJV32 | YJLV32 | XLPE insulation, thin steel-wire armor, PVC sheath power cable | Be applicable to the well, water inside and fall in the bad soil, the cable cans bear the equal dint outside the machine with pull the dint . |
YJV72 | YJLV72 | XLPE insulation, have no the magnetism thick steel-wire armor, PVC sheath power cable | |
YJV42 | YJLV42 | XLPE insulation, thick steel-wire armor, PVC sheath power cable | Be applicable to the well, underwater with the bottom of sea, the cable cans bear the bigger pressure with lead to pull the dint. |
ZR: Means Flame retardent
Type | Nominal cross-sectional area | |||||
Single-core | 2-core | 3-core | 4-core | 5-core | ||
YJV ZR-YJV | YJLV ZR-YJLV | 1.5-800 | 1.5-300 | 1.5-300 | 1.5-300 | 1.5-300 |
YJV22 ZR-YJV22 | YJLV22 ZR-YJLV22 | 10-800 | 4-300 | 4-300 | 4-300 | 4-300 |
YJV32 ZR-YJV32 | YJLV32 ZR-YJLV32 | 10-800 | 4-300 | 4-300 | 4-300 | 4-300 |
Picture
- Q:I have 200 feet of wire run from an electrical box to a electric motor that is not getting enough amps. I am tring not to run a new wire from the breaker box so if I cut the wire a few feet from the box and run a bigger wire say from 10' of 10-2 to 190' of 6-2 will I get less of a drop?
- If the motor you are running is 120 Volts, consider getting a new one. A 240V volt load will draw 1/2 the amperage, and save you from replacing the wiring. You'd have to replace the breaker, and means of disconnect, but should save you some of the grunt work.
- Q:I am installing recessed canister lights in a basement room and I ran into a problem. 3 of the holes that I cut out of the ceiling happened to be right next to several other cables that provide electricity to other parts of the house. The lights in the canisters are 45W R20 bulbs and the canisters themselves are 5 3/8 diameter and will practically touch these lines if I install them in the current holes. Will this canister get hot enough to damage the other wires and cause a dangerous situation or should they be far enough away from the light itself? Also the house is a '91 so the electrical lines should all be 90 c degree temp rating.
- The cannisters will simply absorb the heat. The wire you are adding has a pretty good heat rating and is designed for such applications. I do this stuff all the time. Go for it!
- Q:I have a halogen heater and one of the bulbs in it started flickering so I opened it up disconnected that bulb and found the casing around one of the wires connecting to it was burned off. So I have this exposed wire which is not connected to anything and was thinking about just covering it with duct tape and using the heater again. Now im not stupid and everything about this to me sounds like a bad idea but would like to get a second opinion on exactly how dangerous it would be, it would only be temporary until I got a new heater.
- cut the end off down to the insulation and put a wire nut onto it. every electrical circuit has 2 wires - in and out. what happened to the other end? obviously, u will only get 1/2 the heat unless the bulbs are connected in series, the u will get nothing. I would assume there is a high and low setting - so it will only work on one of them but will always be low.
- Q:1966 Mustang ignition wire seems to be getting too hot and melts any electrical tape on it.
- You really should identify what you mean by ignition wire. However ordinary PVC electrical tape used (say) on spark plug leads, especially near the plugs or distributor ends, will probably come off, just through the heat around the engine, if nothing else. The heat mainly softens the adhesive on the tape, and it unwinds. If you are talking about the wire from the ignition switch to the coil, it is a resistance (ballast) wire, and normally gets warm. However the same comment re the tape applies if the tape is near the ignition coil end.
- Q:i under the house. Does that mean I will need to have the house rewired
- Maybe not rewired but you would have to have a lot of Electrical work done, it may be cheaper to have it rewired then fixed having it fixed would included a lot of wire tracing and a lot of junction boxes set under the house, your best bet would be have a Electrician give an estimate of repair you would have a good idea which would be cheaper then. Hope this Helps
- Q:Hello,In the rental cottage that I live in, I have an enclosed back porch that doesn'tt have any electrical outlets. What I do have is a vent opening for the furnace room which is on the other side of the wall. This is a short vent, and once inside the furnace room, it is just a few feet to an electrical outlet. Since I am renting the place, I figure the most non-invasive way to get electricity out to the porch is to feed an extension cord through the vent. One catch is that I put a screen on the vent because otherwise moths and bees were flying into the house. How can I install the extension cord, through the screen, and reseal the screen so I can stay bug-free inside?thanks much
- Fishing Electrical Wire
- Q:What is the difference between copper and cable used in electrical equipment? Best detail, thank you
- Board and memory is very good, but the CPU is low, there is no cost. I7 or more CPU with DDR1333 memory is worth, with other CPU are wasted.
- Q:The socket has yellow and blue gray three colors, which is the line of fire? Which is the zero line? Which is the ground?
- Cpu with Intel e6600 what the motherboard on the use of medium can best find an acquaintance there is the kind of quotient or the business is easy to kill people
- Q:How are they wired up, and how do they work, thanks.
- If you are talking about a feed meaning a home run from the panel then the feed usually goes to the light and drops to the switch and can pick up a couple of recepticles in the wall also. The national electrical code allows for a white to switch hot if it is marked on both ends so you can use a two wire run. If you run from the panel to the switch box then you will have a hot switched for the light, one for the hot recepticles and a neutral for all. Keep in mind the green is allways used and only used for a bond and nothing else.That gives you a 3 wire and a bond going from the small switch box to the larger light box in the cieling, Which will work but is harder to follow years later if you have problems. If you run from the panel to the cieling box it is easy to locate and trouble shoot all wires as everything goes to that box. Most switches are single pole and require 2 wires and it is pretty much a in and out deal so that is simple enough but if it is a 3 way ( or switched at 2 places ) you have to use 3 way switches, If you want to switch from 3 places or more then you have to use 2 - 3 way and the rest 4 way. I realize I am not telling you all you have to know but electricity is not for people who dont know what they are doing. You can get shocked and others can get hurt or the house could burn down with you sleeping in it so I suggest you get out the Home Depot do it yourself books or go to the library and learn what and the whys of electricity. I hope what I have told you gets you to see that it takes some home work to make it safe and understandable.
- Q:30kw how much cable and switch to use
- 50A circuit breaker simply can not bring 30KW load, 30KW load the normal working current is 50-60A. You have to use 3 * 25 copper cable or 3 * 35 aluminum cable, if the distance is large with a large Model, the open selection of 100A.
1. Manufacturer Overview |
|
---|---|
Location | |
Year Established | |
Annual Output Value | |
Main Markets | |
Company Certifications |
2. Manufacturer Certificates |
|
---|---|
a) Certification Name | |
Range | |
Reference | |
Validity Period |
3. Manufacturer Capability |
|
---|---|
a)Trade Capacity | |
Nearest Port | |
Export Percentage | |
No.of Employees in Trade Department | |
Language Spoken: | |
b)Factory Information | |
Factory Size: | |
No. of Production Lines | |
Contract Manufacturing | |
Product Price Range |
Send your message to us
XLPE Insulated and PVC Sheathed Low Voltage Power Cables
- Loading Port:
- China main port
- Payment Terms:
- TT or LC
- Min Order Qty:
- 100 m
- Supply Capability:
- 20000 m/month
OKorder Service Pledge
OKorder Financial Service
Similar products
New products
Hot products
Related keywords