GW23,170kv high voltage disconnect switch
- Loading Port:
- Qingdao
- Payment Terms:
- TT OR LC
- Min Order Qty:
- 1 unit
- Supply Capability:
- 400 unit/month
OKorder Service Pledge
OKorder Financial Service
You Might Also Like
Specifications
1. Outdoor 145kV AC Bus and Line Disconnectors(ISOLATOR)
2. KEMA test report
3. ISO quality certificate
4. Good quality
General introduction :
GW4-40.5/72.5/126/145/170/252 Ⅲ Series, two columns, horizontally rotating type, HV, AC, disconnector
Product classifications and Main Technical Specifications :
1), Product classification
Voltage level: 40.5kV, 72.5kV, 126kV, 145kV, 170kV, 252kV.
Current level: 630A,1250A, 2000A, 2500A,3150A, 4000A.
Auxiliary earthing switch type: none earthing switch, left earthing switch, right earthing switch, double earthing switches.
2), Main Technical Specifications
Technical Specifications | Product Type | GW4-40.5Ⅲ | GW4-72.5Ⅲ | GW4-126Ⅲ |
Rated voltage kV | 40.5 | 72.5 | 126 | |
The rated current A | 1250, 2000, 3150, 4000 | |||
Disconnector | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Grounding switch | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Rated short-time power frequency withstand voltage (RMS) kV | to earth | 95 | 160 | 230 |
across open contacts | 118 | 200 | 230+70 | |
Rated lightning impulse withstand voltage (peak) kV | to earth | 185 | 350 | 550 |
across open contacts | 215 | 410 | 550+100 | |
minimum clearance in 1 min power frequency withstand voltage when ground blade closing to live part of disconnector | 53 | 94 | 164 | |
rated terminal static mechanic load N | longitudinal level | 1000 | 1000 | 1000, 1250 |
Horizontal level | 750 | 750 | 750 | |
Vertical force | 1000 | 1000 | 1000 | |
switching micro-capacitance current A | 2 | 2 | 2 | |
switching micro-inductance current A | 1 | 1 | 1 | |
switching busbar for current transfer A (busbar transfer voltage 100V) | 400V, 2500A, 100 times | |||
Radio interference level | less than 500 μV | |||
Mechanical life | 3000 | 3000 | 3000 | |
single pole weight (kg) | 120 | 200 | 260 | |
Note: All applied to an altitude of 2000m |
Technical Specifications | GW4-145Ⅲ | GW4-170Ⅲ | GW4-252Ⅲ | |
Rated voltage kV | 145 | 170 | 252 | |
The rated current A | 1250, 2000, 3150, 4000 | |||
Disconnector | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Grounding switch | Rated peak withstand current kA | 100, 125 | ||
Rated short-time withstand current (RMS)kA | 40, 50 | |||
Rated short circuit duration s | 4, 3 | |||
Rated short-time power frequency withstand voltage (RMS) kV | to earth | 275 | 325 | 460 |
across open contacts | 315 | 375 | 460+145 | |
Rated lightning impulse withstand voltage (peak) kV | to earth | 650 | 750 | 1050 |
across open contacts | 750 | 860 | 1050+200 | |
minimum clearance in 1 min power frequency withstand voltage when ground blade closing to live part of disconnector | 188 | 221 | 291 | |
rated terminal static mechanic load N | longitudinal level | 1000, 1250 | 1500 | 1500 |
Horizontal level | 750 | 1000 | 1000 | |
Vertical force | 1250 | 1250 | 1250 | |
switching micro-capacitance current A | 2 | 2 | 2 | |
switching micro-inductance current A | 1 | 1 | 1 | |
switching busbar for current transfer A (busbar transfer voltage 100V) | 400V, 2500A, 100 times | |||
Radio interference level | less than 500 μV | |||
Mechanical life (times) | 3000 | 3000 | 3000 | |
single pole weight (kg) | 300 | 326 | 900 | |
Note: All applied to an altitude of 2000m |
- Q: What are the two power distribution equipment?
- Primary equipment is the equipment used in the main system of transmission, transmission and distribution
- Q: What are the general requirements for working on distribution equipment?
- Common type cable connector used in power distribution equipment
- Q: What is the power equipment in the distribution room?
- The indoor power distribution room with low voltage load is called the power distribution room,
- Q: Transmission system and distribution system
- Simply put, you can distinguish between the end of the cable to the use of electrical equipment (motor, power box) is the distribution system to the substation, transformer is the transmission system
- Q: What is the difference between power supply and distribution
- The two is the integration of power generation and power supply.
- Q: Transmission lines are not electrical equipment?
- If you are satisfied, please accept it as a satisfactory answer
- Q: An introduction to the interpretation of flexible AC transmission systems
- synchronous compensator (STATCOM), reactive power distribution is mainly used to improve the system, to adjust voltage and improve the voltage stability of the system;
- Q: Rural high voltage transmission line equipment ownership
- High voltage transmission line, one end of the power plant (power), the other end of the number of users in the use of electricity, of course, the current
- Q: Difference between distribution voltage and supply voltage
- In general, the city substation will be reduced to 10KV 110KV to the electrical terminal.
- Q: Power distribution equipment should be prepared before the blackout?
- electrician received power outage notice, pull down the knife switch, accept fuse.