Description:

EMT steel Connector

American Standard, NPT Thread

UL Standard 514B

Size: 1/2" to 4"

Material: Steel

Steel emt connectors are used to bond EMT conduit to electrical junction boxes or enclosures. JIACHI EMT steel connectors provide concrete tight connections when taped and properly secured with the included locknut, and are rated for electrical applications above 600 volts. Their heavy gauge steel construction maintains mechanical protection and solid grounding of the conduit to the designated electrical junction box or enclosure. Additionally, EMT conduit connectors are pure steel and zinc plated for excellent corrosion protection.

Applications:

EMT steel connector: Joins steel EMT conduit to Electrical box and enclosure
•Connect & effectively bond EMT conduit to steel outlet boxes, load centers & other metal enclosures
•May be used indoors and in concrete-tight applications when taped
•Body and locknut made with die-cast zinc alloy
•Set screw made with zinc-plated steel
•Tri-Drive screw head design for use with Phillips, slotted and square screwdrivers
•Screw thread is designed to not vibrate loose
•Reversible locknut designed to cut through protective coatings on boxes & enclosures
•UL standard for safety
•Application type : EMT
•Electrical Product Type : Standard Fitting
•Fitting type : Connector
•Indoor/Outdoor : Indoor
•Paintable/Stainable : No
•Material: steel
•Trade Size (in.) : [1/2"] [3/4"] [1"] [1-1/4"] [1-1/2"] [2"][2-1/2"] [3"] [4"]

Specification:

SET SCREW EMT CONNECTOR-STEEL,EMT steel Connector

Pictures:

SET SCREW EMT CONNECTOR-STEEL,EMT steel Connector

 

Production:

 

  

 

Q:Is the cable head made of every building?
Building in accordance with the floor or unit configuration distribution box, there are office buildings using a total box. Where there is a cable out of the situation, must be wrapped to make the cable head, according to the choice of distribution box circuit breaker wiring crimp or not crimp the cable terminal. In other words, the cable head must be made, but not necessarily crimp the cable terminal.
Q:Can the main cable be aluminum cable? And explain why, thank you!
Power board problem cost 10 less than the general maintenance received you 150
Q:The difference between nylon balls and geese and ducks
If the 2.5 square copper wire for the output extension cable, 20 meters distance, the total resistance of about 2 * 1.7 * 0.2 / 2.5 = 0.272 (ohms), the current maximum 1.8A, the voltage drop is 0.272 * 1.8 = ), The charging voltage is 55-0.5 = 54.5 (volts), a difference of about 1% will not have any impact on the battery. However, the third floor, said Ye Hao, you can put the charger put the debris room, from your house put a 220V power cord down, home and then engage in a switch control. It is best to design a light at home, can intuitively see if the electricity is full. That's better. Design light, teach you a way: to find a bad leakless protector, open there is a coil-like ring-shaped stuff, called zero sequence current transformer, it will be down, be careful, do not put Transformers inside the coil hurt, get down, in the transformer two thin lines connected to a light-emitting diode. And then your 220V power cord line of fire from the center of the sensor through, around 3-5 turns. In this way, as long as there is current flow, the light-emitting diode will be bright, when the charge is over, the charging current is close to zero, the light-emitting diode will be extinguished. You can from the light-emitting diode is lit to determine whether the electric has been filled. I also have an electric bike that is so charged.
Q:1000 kW 600 m cable to use much
Such a large load so far away, can only be transported with 10KY, near the installation of the transformer Caixing, if the 380V transmission, cross-sectional area, high cost, loss of large, not worthwhile. 10KV high-pressure delivery, current 55A, with 25mm? copper cable 35mm? aluminum cable delivery on it. If the 380V transmission, according to the line voltage loss simple calculation formula △ U% = PL / CS take △ U% = 5 copper cable S = PL / CS △ U% = 1000X600 / 77X5 = / 385 = 1558mm? aluminum cable S = PL / CS = U06 / 46X5 = / 230 = 2307mm? Line voltage loss △ U Simple calculation formula △ U% = PL / CS △ U% - Percentage of voltage loss P - Active power of conveying (Kw) Distance of L- M) C-constant, aluminum single-phase 8.. aluminum three-phase four-wire 46; copper single-phase 12.. copper three-phase four-wire 77S-conductor cross section (mm?) (quoted from "electrical entrance permit test low pressure Class theory "" electrical engineering basis ")
Q:How do I ask for cable prices? How many tons is one or more?
Cable bridge grounding should belong to the protective grounding, grounding resistance at a cross point is not greater than 50 milliohms, no jumper no more than 5 milliohms
Q:Does anyone know the "line buckle" classification (including shape / size / material / has been some commonly used size!) Line deduction is a hardware products! For daily necessities!
In accordance with the relevant safety regulations, the power cable should not be parallel to the top of the thermal pipe laying, when can not be avoided, the interval distance should not be less than 1000mm, during which should also take effective insulation measures. Power cable and thermal pipe cross, the thermal pipe insulation layer, the separation distance should be not less than 500mm, no insulation layer should not be less than 1000mm, and in the cross with the insulation board to be protected, the length of the insulation board should not be less than d + 2000mm (d for the thermal pipe insulation layer diameter).
Q:How much of the cable with the switch?
The switch is selected according to the current. General switch = (2-2.5) Current three-phase current = P / 1.732 / 0.38 / 0.8 Single-phase current = P / 0.22 / 0.8
Q:25 square copper cable how much money one meter?
3000w electrical work at 220V voltage is about 13.6A (current = power divided by voltage). Copper core line of the working current is generally a square 4-6A. That is to say you use 3-4 square power cord more secure.
Q:3 by 16 cable is a few flat? How? That 5 by 16?
Is the power directly out of the CPU power supply line or on this basis and added the extension line
Q:What is the meaning of PG + digital markings for electrical wiring?
The best cement and other dry in the closing, because the wet cement contains moisture, can be conductive, dry the probability of conduction less. Pay attention to the wire to maintain integrity, no broken skin, it is best to protect the casing.

1. Manufacturer Overview

Location
Year Established
Annual Output Value
Main Markets
Company Certifications

2. Manufacturer Certificates

a) Certification Name  
Range  
Reference  
Validity Period  

3. Manufacturer Capability

a)Trade Capacity  
Nearest Port
Export Percentage
No.of Employees in Trade Department
Language Spoken:
b)Factory Information  
Factory Size:
No. of Production Lines
Contract Manufacturing
Product Price Range

Send your message to us

This is not what you are looking for? Post Buying Request

Similar products

New products

Hot products


Hot Searches

Related keywords