Product Description:

Range summary


The Acme.F range front access valve regulated lead acid batteries is designed with real front access structure. The state-of the-art internal and external design ensures Acme.F the high reliability and makes the installation squite simple and safe when placed on a standard relay rack tray or in a closed cabinet.
 Acme.F range VRLA battery is designed with high energy density and suitable for 19". 23" rack or cabinet.
                                    

Acme.F also offers options of top connection and side of monoblocs connection.

The terminal protector for Acme.F batteries are designed with special probe hole allowing safe and easier voltage testing and suitable for all connection means.

The specially centralized venting system ensures the small gas be vented our of the closed cabinet
                                     

The prmium Acme.F batteries are ensured  the quality with NARADA's QA system according to the ISO90001 and ISO14001 standard.









Technical features

  • Real front-access terminal connections for fast and easy installation and maintenance

  • Easy on easy off multi-purpose design ternimal protector

  • Suitable for 19", 23" racking or cabinet

  • Proven excellent special lead-tin-calcium formula alloy for grids and plates

  • Mircoporous glass mats in low resistance as separator

  • Flame retardant ABS material container and cover compliant with UL94 V-0

  • Self-regulating pressure relief valve

  • 12+ years expectant Life under full  float service at 68oF(20oC)

Type:

  12NDT180

Voltage:

  12V

Nominal Capacity:

  180Ah(C10)  180Ah(10 hours rate:)

Length:

  558mm

Width:

  125mm

Height:

  316mm

Height  with termial:

  316mm

Weight:

  60Kg

 

Compliant standards
Designed to be compliant with:

  • IEC 60896-2

  • BS 6290 Part 4

  • Telcordia SR-4228

  • EUROBAT GUIDE

  • UL

  • Manufactured under system ISO9001 & ISO14100 by NARADA

Battery installation compliant with:

EN 50272-2 or local equivalents

Main applications

  • Telecom standby and cyclical applications

  • UPS

  • Power system

Products characteristics:

  • Recommended float charge voltage for 12V battery: 2.25Vpc at 77oF(25oC)

  • Self discharge rate: < 2% pre month at 77oF(25oC)

  • Design life: more than 12 years at 68oF(20oC)

  • Shelf life: 6 months at 68oF(20oC)

  • Valve regulated system, no water addition needed

FAQ 

How long a battery can last?

The service design life of a battery are vary considerably with how it is used, how it is maintained and charged, temperature, and other factors.


Are lead acid batteries recyclable?

Lead acid batteries are 100% recyclable. Lead is the most recycled metal in the world today. The plastic containers and covers of old batteries are neutralized, reground and used in the manufacture of new battery cases. The electrolyte can be processed for recycled waste water uses. In some cases, the electrolyte is cleaned and reprocessed and sold as battery grade electrolyte. In other instances, the sulfate content is removed as Ammonia Sulfate and used in fertilizers. The separators are often used as a fuel source for the recycling process.


What is battery cycle life?

One cycle of a battery is a discharge from full charge to full discharge and a return to full charge again. The total number of cycles a battery can perform before failure is called its Cycle Life. Moat battery manufacturers will not discus the Cycle Life of their product. Many advertised Deep Cycle batteries have not been tested, or, which is the case with cranking batteries, were never designed for long Cycle Life .

 

Send a message to us:

Remaining: 4000 characters

- Self introduction

- Required specifications

- Inquire about price/MOQ

Q:How to determine the battery is good or bad?
Instrument test: the general use of battery discharge tester, the test instrument two positive and negative clamp were holding the battery positive and negative electrodes, press the test button to observe the test instrument instructions.
Q:How does the battery increase the voltage?
The so-called battery is the storage of chemical energy, if necessary, the release of electrical energy of an electrical chemical equipment.
Q:80ah how much battery storage capacity?
The size of the battery storage power refers to the battery capacity. Battery capacity is generally calculated in AH (safety). You 80Ah battery capacity is 80Ah, meaning that if you discharge current to 80A, you can put an hour.
Q:How to repair the battery?
To the battery in accordance with the 0.1C current discharge, record the discharge time. Its discharge current multiplied by the number of hours of time, is the battery repair capacity. If the Chongqing battery capacity to reach the nominal capacity of more than 70%, the end of the repair.
Q:Battery 200ah / 104 what does that mean?
This should be refers to 2V200AH battery 104, power with the 220V.
Q:What is the meaning of the battery above 12v65Ah?
12V is said to be the voltage, 65Ah is the current. (A is the unit of current. H is the time unit .1 hours.)
Q:Lead-acid battery how to maintain?
After passing the test, cover the exhaust cutting, pay attention to restore the filler, cover the battery cover, if the cover is glued, then glue bonding.
Q:What are the hazards of battery over discharge?
The battery discharge to the standard termination voltage when the internal resistance will become larger, the battery electrolyte concentration will become very thin, especially the battery plate micropores and battery plate surface these two points are almost neutral; battery over discharge because of Internal resistance will become larger, so the battery will appear inside the phenomenon of heat, the battery volume will appear fever expansion.
Q:How does battery activation work?
If you are talking about dry batteries, that is, to add sulfuric acid can use the battery (commonly known as water bottles), then it is because the long-term storage so that a high degree of oxidation of the negative board, plus acid will be a high temperature, Low, you can add acid in the pool after the addition of a small current for a long time to charge, you can solve. Generally with 0.05C charge to 3 times can be.
Q:What kind of battery is divided into?
Ordinary battery: ordinary battery plate is composed of lead and lead oxide, the electrolyte is sulfuric acid aqueous solution. Its main advantage is the voltage stability, the price is cheap.

1. Manufacturer Overview

Location
Year Established
Annual Output Value
Main Markets
Company Certifications

2. Manufacturer Certificates

a) Certification Name  
Range  
Reference  
Validity Period  

3. Manufacturer Capability

a)Trade Capacity  
Nearest Port
Export Percentage
No.of Employees in Trade Department
Language Spoken:
b)Factory Information  
Factory Size:
No. of Production Lines
Contract Manufacturing
Product Price Range