Technical specifications

Table 2.3: Technical Parameters of QD200 Series Frequency Inverters

ITEM

SPECIFICATIONS

Main

Input

Rated voltage and frequency

Single-phase 200V class:  200V-240V,50Hz/60Hz

3-phase 400V class:  380V-480V , 50Hz/60Hz

Allowable value of change

Voltage: 380V-15% ~ 480V+10%;  Frequency: ±15%

Main output

Output voltage

Maximum output voltage equals to input voltage

Output frequency

0.5 Hz to 400 Hz

Overload capacity

150% of rated output current for 60s, 200% of rated output current for 2s

Control performance

Modulation mode

3-phase PWM, 2-phase PWM

Control mode

V/f control for constant torque, V/f control for quadratic load, vector control without PG (open loop control),Energy-saving

Setting method of run command

Outer terminal, keyboard panel or serial communication

Setting method of speed command

Analog setting, keyboard, serial communication, UP/DOWN speed setting from external terminal

Speed setting resolution

Keyboard: 0.1 Hz

Analog setting: 0.05/50Hz (10bit)

Speed control precision

V/f control:±2%

vector control without PG (open loop control): ±0.2%

Speed control range

V/f control 1:40

vector control without PG (open loop control)  1:200

Acceleration and Deceleration

Time

0-3200.0s

switching frequency

1.5 kHz ~ 12 kHz, according to junction temperature automatically reduce the switching frequency

Analog input

Number

2 ways: AI1、AI2

Type

DC voltage or DC current

Maximum input range

AI1: 0 to 5VDC, 0 to 10VDC, 0/4 to 20mA DC receivable

AI2: 0 to 10VDC or PTC probe input receivable

Analog output

Number

1 way: AO1

Type

DC voltage or DC current

Maximum input range

Voltage output: 0 to 10V, Current output: 0/4 to 20mA

logic input

Number

0.75kw-11kW:LI1,LI2,LI3,LI4,AI1,AI2

15kW-500kW:LI,LI2,LI3,LI4,LI5,LI6,LI7,LI8,AI1,AI2

note:2 virtual logic input, capable of configuring AI1 and AI2 into logic input port (positive logic or negative logic)

Type

Source or Sink

Maximum input range

0-24VDC

ITEM

SPECIFICATIONS

logic output

Number

0.75kW-11kW: pulse signal output (LO-CLO)、relay output 1(T1A、T1B、T1C

15kW-500kW:pulse signal output(LO-CLO)、relay output 1、2(T1A-T1B-T1C、T2A-T2B-T2C

pulse signal output

OC,output frequencycurrentoutput、ect other function

relay output

RA-RB-RC, including a NO contact and a NC contact

Maximum switch capacity:

T1A,T1B: 3A at 250VAC, or 4A at 30VDC

T2A,T2B: 2A at 250VAC or 30VDC

Serial communication interface

RS485 interface supports Modbus protocol.

Display

4-digit LED digital display

For display of frequency setting, output frequency, fault code and parameter setting etc.

Environment

Standard

Development of VSC200 series frequency inverters follows strict international standards and relevant recommended IEC and EN standards for control devices, especially IEC/EN61800-5-1 and IEC/EN61800-3.

Altitude

Derating unnecessary when altitude is 1000m or below (Derating necessary at altitude higher than 1000m)

Ambient environment

0.75kW-11kW: Reliable operation at -10 ~ 50°C without derating. When top protective cover is taken off, the environment temperature can be as high as +50 °C. Above +50 °C, the current drops by 2.2% for each rise of 1 °C in temperature. 15kW-500kW: Reliable operation at -10 ~ 40°C without derating.

Storage: -25 ~ 70°C

Humidity

No condensed water or drip at 5 ~ 95%, In accordance with IEC60068-2-3

Impact strength

15gn for continuous 11ms, In accordance with IEC/EN60068-2-27

Maximum antipollution capacity

Class 2, in accordance with IEC/EN61800-5-1

Structure

Protection level

Top: IP41 (without removing the protective top cover). Other parts: IP20

Cooling Method

Forced Air cooling

Installation method

Wall mounted

Send a message to us:

Remaining: 4000 characters

- Self introduction

- Required specifications

- Inquire about price/MOQ

Q:Speed regulation method of three - phase asynchronous motor
Change the number of pole pairs can be adjusted, in the way around the stator coil through the tap method can achieve two-speed. With the popularity of the inverter, three-phase asynchronous motor speed mostly with the inverter.
Q:What is the frequency of `30 points
frequency conversion By changing the AC frequency of the way to achieve AC power control technology is called frequency conversion technology
Q:How does the laptop's power adapter open
Control Panel - System - Hardware - Device Manager - Network Adapter, right click, and the menu appears. If it is infinite, then first follow the above argument to see if it can be enabled.
Q:Motor 2 pole and 4 pole in the inverter with what set to show
The inverter has a parameter that requires you to enter the number of motor poles, see the direct input of the number of poles
Q:Quartet of the TA, TC terminals have positive and negative?
The TC terminal has no positive and negative poles, which are passive programmable relays
Q:What is the difference between variable frequency motor and variable speed motor?
The variable frequency motor requirements are high, are special motor, so the general motor can not use the inverter to speed. According to the above formula, it can be seen that increasing the frequency, the motor speed will be faster, reduce the frequency of the motor speed is slow, variable frequency motor core is also a special material, because the ferromagnetic material There is a saturation period, to the saturation period, regardless of whether the motor current increases, the motor will not continue to increase the intensity of the magnetic field,
Q:Laptop power adapter in the ring is how is it?
Is the voice of the transformer, do not have to buy, will be used on the line.
Q:Fuji inverter motor set the number of poles will not have any effect?
The number of motor poles set incorrectly, self-learning when the motor parameters are not correct, not the correct parameters of the motor. Inverter control speed is not accurate, and the motor will heat, can not work properly.
Q:A 4-pole AC motor into a 2-pole AC motor, the motor is controlled by the inverter, to make the maximum speed of the 2-pole motor and the original 4-pole
The upper limit frequency transferred to 25HZ, the number of poles changed to 2, try to run when the motor speed test
Q:There is no inverter comes with simple PLC programming function
Inverters are generally digital input, and analog input, a digital output, etc., can also be controlled by means of communication. Digital input can be used as a positive and negative and reset the alarm, the analog input can be given as a speed, and how to use the inverter to see the specific model. Take the Siemens inverter, MicroMaster420,567 terminal 3 digital input, 8 for the 24V, 9 for the 0V, you can usually open the point on the 8th 24V back to 567, as a digital input, you can also directly into the switching power supply Of the 24V, but the switch power supply 0V and 9 terminals connected to the potential, or the inverter may not be able to identify the outside world 24V. (DP communication, USS communication, etc.), with the terminal input on the P0700 = 1, the user can set the command source, the panel can be input, 2, P0701 to P0703 corresponding to the three digital functions: parameters set to 1 forward, 2 for the reverse ... ... a lot of features and control methods, see the corresponding product manual like

1. Manufacturer Overview

Location
Year Established
Annual Output Value
Main Markets
Company Certifications

2. Manufacturer Certificates

a) Certification Name  
Range  
Reference  
Validity Period  

3. Manufacturer Capability

a)Trade Capacity  
Nearest Port
Export Percentage
No.of Employees in Trade Department
Language Spoken:
b)Factory Information  
Factory Size:
No. of Production Lines
Contract Manufacturing
Product Price Range